Fuses

The following varieties of fuses can be offered against the requirements:

CT / PT Range :

Voltage rating:
Families : 3.3/3.6kV, @ 40kA breaking capacity
6.6/7.2kV, @ 40kA breaking capacity
11/12kV, @ 30kA breaking capacity
33/36kV @ 20kA breaking capacity
Current rating : 0.1A, 1.5A, 2A, 3/ 3.3A, 4A, 5.1A & 6.,3A (in all voltage ratings)
Body size : 25.4mm (1inch) / 22mm
Filler type : High quality fine Quartz
Fusing range : as per IEC 282-1 / BSEN282-1/ equivalent std/ specs of custom designed.


The CT / PT fuses of our range shall comprise with close matched fusing & non fusing characteristics, to offer a close & finer protection for the equipment and/ or installations. Standard fusing curves start with 1.5In (In- normal rating current) and multiple currents thereof, but any closer matching to the equipment characteristics can be supplied as well.

Application:
The CT/ PT fuses are applicable in use as incomer units at the switch fuse units in the front end of the installation. The CT/ PT range of fuses can also be offered in oil filled categories if needed.

Please consult the factory for type references and prices and for any special requirements in terms of tag/ body & performance characteristics.

HV Range of fuses (BSHV type) :

Voltage rating:
Families : 3.3/3.6kV, @20kA breaking capacity
6.6/7.2kV, @20kA breaking capacity
11/12kV, @20kA breaking capacity
33/36kV @20kA breaking capacity
Current rating : 1, 6.3, 10, 16, 20, 25, 32, 40 (2inch body size),
40, 50, 63A (2.5inches)
63, 80, 100A (3inches)
in all voltage ratings
Body size : 2inches(50.8mm) / 2.5inches(63.5mm), 3inch (76.2mm)
Filler type : High quality fine Quartz
Fusing range : as per IEC 282-1 / BSEN282-1/ equivalent

 

The HV fuse range (BSHV) is offered in 3 different body sizes, viz., 2inch (50.8mm), 2.5inch(63.5mm) & 3inch(76.2mm) with current ranges up to 40A (2inch), 63A(2.5inch), 100A(3inch) & varying fixing distances as called in by the standard.
Standard fusing curves start with 1.8In and multiple currents thereof, but any closer matching to the equipment characteristics can be supplied as well. The HV range of fuses can also be offered in any special characteristics if needed. Consult the factory for your requirements of technical characteristics and the type references offered.

Application:
These fuses are applicable in use as incomer units at the switch fuse units in the front end of the installation on HV fuse gear/ switchgear side/ line transmissions. The HV BS range of fuses can also be offered in varying time current/ fusing characteristics if needed.

HV Range of fuses (HV-DIN type) :

Voltage rating:
Families : 3.3/3.6kV, @20kA breaking capacity
6.6/7.2kV, @20kA breaking capacity
11/12kV, @20kA breaking capacity
33/36kV @20kA breaking capacity
Current rating : 1, 6.3, 10, 16, 20, 25, 32, 40 (2inch fuses),
40, 50, 63A (2.5inches)
63, 80, 100A (3inches)
in all voltage ratings
Body size : 2inches(50.8mm) / 2.5inches(63.5mm), 3inch (76.2mm)
Filler type : High quality fine Quartz
Fusing range : as per IEC 282-1 / BSEN282-1/ equivalent

 

The HV fuse range (HV-DIN) is offered in 3 different body sizes, viz., 2inch (50.8mm), 2.5inch(63.5mm) & 3inch(76.2mm) with current ranges up to 40A (2inch), 63A(2.5inch), 100A(3inch).
These fuses can go in to Standard Fuse Bases / Fuse fittings. Standard fusing curves start with 1.8In and multiple currents thereof, but any closer matching to the equipment characteristics can be supplied as well. The HV range of fuses can also be offered in any special characteristics if needed. Consult the factory for your requirements of technical characteristics and the type references offered.

Application:
The HV BS-DIN range of fuses can also be offered in varying time current/ fusing characteristics if needed. These fuses are applicable in use as incomer units at the switch fuse units in the front end of the installation on HV fuse gear/ switchgear side.

LV Range of fuses (LVBS type) :

Voltage rating:
Families : 240/415V @80kA breaking capacity
Current rating : 2,4,6, 10, 16, 20, 25, 32, 40, 50, 63, 80A, 100A, 120A, 160A, 200A, 250A, 315A, 355A, 400A in round bodied variants.
As per IEC 269-2-1/IS: 13703 pt. 2 sec.1
Body size : Varying body sizes as specified by IEC 269-2-1/IS: 13703 pt. 2 sec.1
Filler type : High quality fine Quartz
Fusing range : as per IEC 269-1 / BSEN269-1/ IS: 13703 Pt.2/ sec.1

 

The LV fuse range (BSLV) is offered in varying different body sizes, and in multiple current ratings from 2A until 400A @ 240/ 415Volts applications.

Standard fusing curves start with 1.25In (In- normal current), and multiple currents thereof. The LV range of fuses can be offered in any special tag / fixing sizes of interest.

Applications:

The LV fuses finds application in independent installations or as well in control panel applications. Can be used in bare or closed environment (with applicable derating) or in switch fuse units as necessary.

Consult the factory for your requirements of technical characteristics and the type references offered.

LV Range of fuses (LV-DIN type) :


Voltage rating:
Families : 240/415V @80kA breaking capacity
Current rating :

6, 10, 16, 20, 25, 32, 40, 50, 63,80A, 100A, 120A, 160A, 200A, 250A, 315A, 355A, 400A in square bodied variants. as per IEC 269-2-1/IS: 13703 pt. 2 sec.1

Body size : NH000 (up to 40A max)...(1)
NH00 (up to 63A max)...(2)
NH0 (up to 80A max)....(3)
NH01 (up to 160A max)....(4)
NH02 (up to 250A max)....(5)
NH03 (up to 400A max)....(6)

Varying square body sizes (as per the NH size) and as specified by the standard listed above.

Filler type : High quality fine Quartz
Fusing range : as per IEC 269-1 / BSEN269-1/ IS: 13703 Pt.2/ sec.1

 

The LV fuse range DIN type (BSLV-DIN) is offered in varying different body sizes, and in multiple current ratings from 6A until 400A @ 240/ 415Volts application.

Standard fusing curves start with 1.25In (In- normal current), and multiple currents thereof. The LV range of fuses can be offered in any special tag / fixing sizes of interest.

Applications:
The LVBS (DIN type) fuses finds application in independent installations or as well in control panel applications. Can be used in bare or closed environment (with applicable derating) or in switch fuse units as necessary. It is to be used in the intended fuse fitting/ base as necessary.

Consult the factory for your requirements of technical characteristics and the type references offered.

Note : Sl. Nos. 1,2,3,4,5,6 (red color) ----- to be reconsidered for exact type reference per the factory needs.